SEWAGE DISPOSAL STATION #3

Sewage disposal station #3: this disposal station is situated in Aatchi Abadi near boundary wall of University area.

The trunk sewer AA/ joins to this disposal station. The hydraulic calculations for the trunk sewer AA/ are carried out in the table. The sewage flow from Katchi Abadi also fell at this disposal station which is shown in the fig.5.3

 

 

 

 

 

 

 

Sewer AA/

Descriptive

Population

Avg.

Peak

Storm

Design

Design

Exist.

Remarks

Category

 

Daily

Flow

Allowance

Flow

dia 

dia 

 

 

 

Flow

 

 

 

 

 

 

(Person)

(m3/d)

(m3/d)

(m3/d)

(m3/d)

(mm)

(mm)

 

Umer Hall

170

25.704

102.82

102.82

231.34

 

 

 

c – Hall

110

16.64

66.6

66.6

149.76

 

 

 

28 - Servant

224

63.51

254.1

254.1

571.6

 

 

 

Quarters

 

 

 

 

 

 

 

 

4 E – type

32

9.07

36.3

36.3

81.63

 

 

 

House

 

 

 

 

 

 

 

 

4 H types

32

9.07

36.3

36.3

81.63

 

 

 

Quarters

 

 

 

 

 

 

 

Under Sized

ID type

8

2.27

9.08

9.08

20.43

 

 

 

house

 

 

 

 

 

 

 

 

12 c Class

96

27.22

108.78

108.78

245

 

 

 

quarters.

 

 

 

 

 

 

 

 

12 - Single

96

27.22

108.78

108.78

245

 

 

 

Story Servant

 

 

 

 

 

286

225 

 

quarters.

 

 

 

 

 

 

 

Work shop

150

5.67

22.71

22.71

51

 

 

 

Main block

100

3.79

15.14

15.14

34.11

 

 

 

Math. Dept.

100

3.79

15.14

15.14

34.11

 

 

 

New Mechanical

200

7.57

30.28

30.28

68.13

 

 

 

Dept.

 

 

 

 

 

 

 

 

I -B type

8

2.27

9.08

9.08

20.43

 

 

 

House

 

 

 

 

 

 

 

 

Cafeteria

50

1.89

7.57

7.57

17

 

 

 

 

 

 

Shops

15

0.57

2.27

2.27

5.13

50 - c class

400

113.55

454.2

454.2

1021.95

 

 

 

quarters.

 

 

 

 

 

 

 

 

I.F type

8

2.27

9.08

9.08

20.43

 

 

 

Old dispensary

50

7.57

30.28

30.28

68.13

 

 

 

3 – D type houses

24

6.81

27.25

27.25

61.29

 

 

 

12 - c class quart.

96

27.25

109.01

109.01

245.25

 

 

 

Mosque

100

3.79

15.14

15.14

34.11

 

 

 

Alumni house

8

2.27

9.08

9.08

20.43

 

 

 

Table # 4.10

Sum =3328 m3/d

Q = 0.0214 m3/s

Wet well and pump at disposal station #3:

This wet well contains the discharge of sewer AA which is 3328 m3/day (0.0385 m3/s)

The discharge from Katchi Abadi is 1941.71 m3/d (0.0225 m3/s), so total discharge is 0.061 m3/s the design capacity is wet well is given by the following formula:

V =Tmin * Q/4

Tmin = 10 min

So design capacity of wet well =10*60*0.061 =9.15 m3

Existing capacity of wet well =24.48 m3s

Comments:

The capacity of wet well is all-right even it is too much as head is concerned.

Table 5.11

Total Sewage

Designed

Existing

Pump

Designed

 

Existing

 

Flow in Wet Well

Capacity of

Capacity

Capacity

Suction

Delivery

Suction

Delivery

 

Wet Well

 

 

Pipe

Pipe

Pipe

Pipe

 

 

 

 

 

 

 

 

0.061

9.15

24.48

0.0283

300

225

100

100

m3/s

m3

m3

m3/s

mm

mm

mm

mm

 

 

 

 

 

 

 

 

 

 

 