NATIONAL BOARD OF FIRE UNDERWITERS
PUMPER TEST RESULTS

MANUFACTURER: Ahrens-Fox Fire Engine Company's 500-gallon
pumping engine with booster tank and hose body
MUNICIPALITY: Demonstrator DATE: June 18, 1935
CONDUCTED BY: National Board of Fire Underwriters, G.P. Cook, Engineer
MANUFACTURER'S TYPE: WC NUMBER: 9001
ENGINE: MAKE: Ahrens-Fox/Hercules NUMBER: _________
Size Cyl. and Stroke: 4-1/2" x 4-3/4" No. Cyls.: 6 Comp. Ratio: 4.77 to 1
PEAK SPEED: __________ H.P. (A.L.A.M.): __________
PUMP: MAKE: Ahrens-Fox Model: __________ No.: __________
Displacement: __________ TYPE: Single-stage centrifugal with impeller
GEAR RATIO, ENGINE TO PUMP: Capacity: 1 to 2.208 Pressure: __________
Contract Requirements: 500 gallons per minute at 120 lbs. net pressure.
250 gallons per minute at 200 lbs. net pressure.
167 gallons per minute at 250 lbs. net pressure.
Tested at: Draft, Cincinnati, Ohio Lift: 4 feet
First Test:
Duration: 6 hours
Layout of Hose and Nozzles: one 50' line 2-1/2" cotton rubber-lined hose into deluge set with 1-1/2" nozzle tip. Gate throttled.
Average Discharge and Pressure: 508 gallons per minute at 124 lbs. net.
Average Nozzle Pressure: ________ lbs.
Speed, R.P.M.: Engine: _____1428________ Pump: 3150
Gear Ratio Used: ______________________ Pump Operation: __________
Displacement: ________________ Slip: __________
Remarks:
Second Test:
Duration: 3 hours
Layout of Hose and Nozzles: one 100' line 2-1/2" cotton rubber-lined hose into 1" nozzle tip. Gate throttled.
Average Discharge and Pressure: 256 gallons per minute at 203 lbs. net.
Average Nozzle Pressure: ________ lbs.
Speed, R.P.M.: Engine: _____1812________ Pump: 4000
Gear Ratio Used: ______________________ Pump Operation: __________
Displacement: ________________ Slip: __________
Remarks:
Third Test:
Duration: 3 hours
Layout of Hose and Nozzles: one 100' line 2-1/2" cotton rubber-lined hose into 1" nozzle tip. Gate throttled.
Average Discharge and Pressure: 175 gallons per minute at 253 lbs. net.
Average Nozzle Pressure: ________ lbs.
Speed, R.P.M.: Engine: _____2010________ Pump: 4430
Gear Ratio Used: ______________________ Pump Operation: __________
Displacement: ________________ Slip: __________
Remarks:
GENERAL REMARKS (As to performance and condition of machine
during and after test):
Performance satisfactory. Draft test with ample power in reserve.
Signed,
                                                The Ahrens-Fox Fire Engine Company
By: