![]() |
Home |
APS |
Sites |
ABdA |
Help |
![]() |
WEEK 16: POWER SYSTEMS: INTRODUCTION Sections: Intro | Positive | Negative | Zero Introduction. The line-to-ground voltages at the fault is designated as VA, VB and VC. Before the fault occurs, the line-to-neutral voltage of phase a is called Vf, which is a positive-sequence voltage since the system is assumed to be balanced. Since linearity is assumed in drawing the sequence entworks, each of the networks can be replaced by its Thévenin equivalent between the two terminals composed of its reference bus and the point of application of the fault. The current components, IA1, IA2, and IA0 flow out of their respective sequence networks and out of the equivalent circuits of the networks at the point of application of the fault. The matrix equations for the symmetrical components of voltages at the fault is the same as in unloaded generators except that Vf replaces EA. Sections: Intro | Positive | Negative | Zero Power System: Positive-Sequence The internal voltage of the single generator of the equivalent circuit for the positive sequence is Vf, the prefault voltage to neutral at the point of application of the fault. The impedance Z1 of the equivalent circuit is the impedance measued between point of application of the fault and the refernce bus with all the internal emfs short-circuited. The values of Z1 is dependent on the reactances used in the network. The subtransient reactances of generators and 1.5 times the subtransient reactances of synchronous motors or the transient reactances of the motors are the values used to calculate the symmetrical fault to be interrupted. The equation for the positive component of the voltage drop from point of application of the fault to the reference bus (or ground) is: VA1 = Vf - IA1 Z1
Sections: Intro | Positive | Negative | Zero Power System: Negative-Sequence Since no negative-sequence currents are flowing before the fault occurs, the prefault voltage between the point of application of the fault and the reference bus is zero. Therefore, no emfs appear in the equivalent circuits of the negative-sequence network. The impedance Z2 is measured between the point of application of the fault and the reference bus in the network and depend on the location of the fault. The equation for the negative component of the voltage drop from point of application of the fault to the reference bus (or ground) is: VA2 = - IA1 Z1
Sections: Intro | Positive | Negative | Zero Since no zero-sequence currents are flowing before the fault occurs, the prefault voltage between the point of application of the fault and the reference bus is zero. Therefore, no emfs appear in the equivalent circuits of the zero-sequence network. The impedance Z0 is measured between the point of application of the fault and the reference bus in the network and depend on the location of the fault. The voltage drop of zero-sequence impedance from point a to ground is -3IA0ZN - IA0Zg0 Thus the total zero-sequnce impedance through which IA0 flows is ZA0 = 3ZN + Zg0 The equation for the zero component of the voltage drop from point of application of the fault to the reference bus (or ground) is: VA0 = - IA0 Z0
Sections: Intro | Positive | Negative | Zero In matrix form, the three formulas given above would be: |