WEEK 18: POWER SYSTEMS: LINE-TO-LINE FAULTS Sections: Conditions | Network | Example | Problem Set Conditions at Fault. The following are the conditions for line-to-line fault for power system:
VA = 0 Current. The following are the current relationships during a line-to-line fault for power system: In matrix form:
IA0 = 0 Voltage. The following are the voltage relationships during a line-to-line fault for power system: In matrix form: VA1 = VA2
In matrix form:
Sections: Conditions | Network | Example | Problem Set Sections: Conditions | Network | Example | Problem Set A salient pole generator is rated 20MVA, 13.8 kV and has a direct-axis subtransient reactance of 0.25 unit. The negative- and zero-sequnce reactances are 0.35 and 0.10 per unit. The neutral of the generator is grounded. Find the subtransient current in the generator and the line-to-line voltages for subtransient conditions when a line-to-line fault occurs at the generator terminals with the generator operating unloaded at rated voltage. Neglect resistance. Solution: IA1 = Vf / [ Z1 + Z2 ] = 1 + j0 / [ j0.25 + j0.35 ] = -j1.667 p.u. IA1 = IA2 = -j1.667 p.u. IA = IA1 + IA2 + IA0 = 0 p.u. IB = a²IA1 + aIA2 + IA0 = a²(-IA2) + aIA2 + IA0 IB = -IC = -(-2.866 +j0 p.u.) = 2.866 + j0 p.u. Base Current = MVA / [Ö3) x kV ] = 20,000 / [Ö3) x 13.8 ] = 837 amperes. Subtransient Current Symmetrical components of voltage from point a to ground are: line-to-line voltages: Line-to-line voltages: The equivalent line-to-line voltages, would be: Sections: Conditions | Network | Example | Problem Set Solve the following problems 2. Determine the ohms of inductive reactance to be inserted in the neutral connection of the Generator in Problem no. 1 to limit the subtransient line current for a line-to-line fault to that for a three-phase fault. 3. How many ohms of resistance in the neutral connection of the generator in Problem No. 1 would limit the subtransient line current for a line-to-line fault to that for a three-phase fault? 4. A generator rated 100 MVA, 20 kV has X" = X2 = 20% and X0 = 5 %. Its neutral is grounded through a reactor of 0.32 W. The generator is operating at rated voltage without load and is disconnected from the system when a line-to-line fault occurs at its terminals. Find the subtransient current in the faulted phase. |