![]() |
Home |
APS |
Sites |
ABdA |
Help |
![]() |
WEEK 11: INTRODUCTION TO FAULTS Sections: Intro | Positive | Negative | Zero Unloaded Generator: Introduction Introduction. The impedance of a circuit when positive-sequence currents alone are flowing is called the impedance to positive-sequence current. When only negative-sequence currents are flowing, the impedance is called the impedance to negative-sequence current. When only zero-sequence currents are present, the impedance is called the impedance to negative-sequence current. The analysis of an unsymmetrical fault on a symmetrical system consists in finding the symmetrical components of thee unbalanced currents that are flowing. Consider the following schematic: Circuit diagram of an unloaded generator grounded through a reactance. The emfs of each phase are Ea, Eb and Ec. Sections: Intro | Positive | Negative | Zero The generated voltage are of positive sequence only, since the generator is designed to supply balanced three-phase voltages. Thus, the positive-sequence network is composed of an emf in series with the positive-sequence impedance of the genreator. The generated emf is the no-load terminal voltage to neutral, which is also equal to the transient, and subtransient internal voltages since the generator is not loaded. The reactance in the positive-sequence network is the subtransient, transient, or synchronous reactance, depending on whether subtransient, transient, or steady-state conditions are being studied. The reference bus for the positive-sequence network is the neutral of the generator. The neutral of the generator is at ground potential if there is a connection between neutral and ground having a finite or zero impednace since the connection will carry no positive-sequence current. The equation for the positive component of the voltage drop from point a of phase a to the reference bus (or ground) is: Va1 = Ea - Ia1 Z1
Sections: Intro | Positive | Negative | Zero The negative sequence contains no emfs but include the impedances of the generator to negative-sequence currents. The reactance in the negative-sequence network is the subtransient, transient, or synchronous reactance, depending on whether subtransient, transient, or steady-state conditions are being studied. The reference bus for the negative-sequence network is the neutral of the generator. The neutral of the generator is at ground potential if there is a connection between neutral and ground having a finite or zero impednace since the connection will carry no negative-sequence current. The equation for the negative component of the voltage drop from point a of phase a to the reference bus (or ground) is: Va2 = - Ia2 Z2
Sections: Intro | Positive | Negative | Zero The negative sequence contains no emfs but include the impedances of the generator to zero-sequence currents. The reactance in the zero-sequence network is the subtransient, transient, or synchronous reactance, depending on whether subtransient, transient, or steady-state conditions are being studied. The current flowing in the impedance Zn between neutral and ground is 3Ia0. The voltage drop of zero-sequence impedance from point a to ground is -3Ia0Zn - Ia0Zg0 Thus the total zero-sequnce impedance through which Ia0 flows is Za0 = 3Zn + Zg0 The equation for the zero component of the voltage drop from point a of phase a to the reference bus (or ground) is: Va0 = - Ia0 Z0
Sections: Intro | Positive | Negative | Zero In matrix form, the three formulas given above would be: |