TABLE. PERFORMANCE DATA FOR 60-CYCLE SINGLE-PHASE DISTRIBUTION TRANFORMERS, 2,400 TO 4,800 VOLTS TO 120/240 or 240/480 VOLTS
Click here to return to Design Notes.
KVA |
Loss, watts,at 75C |
Per cent efficiency |
Per cent regulation |
Core |
Copper |
Full load |
¼ full load |
PF=1.0 |
PF = 0.8 |
1½ |
20 |
48 |
95.8 |
94.2 |
3.2 |
4.48 |
3 |
27 |
71 |
96.8 |
96.0 |
2.4 |
3.36 |
5 |
37 |
104 |
97.2 |
96.6 |
2.2 |
3.08 |
7½ |
50 |
142 |
97.5 |
96.9 |
2.0 |
2.80 |
10 |
59 |
183 |
97.6 |
97.2 |
1.9 |
2.66 |
15 |
80 |
253 |
97.8 |
97.5 |
1.8 |
2.52 |
25 |
120 |
376 |
98.0 |
97.7 |
1.6 |
2.25 |
37½ |
155 |
495 |
98.3 |
98.0 |
1.4 |
1.96 |
50 |
190 |
605 |
98.4 |
98.1 |
1.3 |
1.82 |
75 |
290 |
905 |
98.4 |
98.1 |
1.3 |
1.82 |
100 |
380 |
1,175 |
98.5 |
98.2 |
1.3 |
1.82 |
150 |
575 |
1,670 |
98.5 |
98.2 |
1.3 |
1.82 |
200 |
820 |
2,050 |
98.6 |
98.1 |
1.2 |
1.70 |