TABLE. PERFORMANCE DATA FOR 60-CYCLE
SINGLE-PHASE DISTRIBUTION TRANFORMERS,
2,400 TO 4,800 VOLTS TO 120/240 or 240/480 VOLTS


Click here to return to Design Notes.

KVA

Loss, watts,at 75C

Per cent efficiency

Per cent regulation

Core

Copper

Full load

¼ full load

PF=1.0

PF = 0.8

20

48

95.8

94.2

3.2

4.48

3

27

71

96.8

96.0

2.4

3.36

5

37

104

97.2

96.6

2.2

3.08

50

142

97.5

96.9

2.0

2.80

10

59

183

97.6

97.2

1.9

2.66

15

80

253

97.8

97.5

1.8

2.52

25

120

376

98.0

97.7

1.6

2.25

37½

155

495

98.3

98.0

1.4

1.96

50

190

605

98.4

98.1

1.3

1.82

75

290

905

98.4

98.1

1.3

1.82

100

380

1,175

98.5

98.2

1.3

1.82

150

575

1,670

98.5

98.2

1.3

1.82

200

820

2,050

98.6

98.1

1.2

1.70