UL

Markings Required for IEC - Based Zone Certifications

 

U.S.

Canadian

IEC

European

a)

Class I

Class I (optional)

------

------

b)

Zone 0, 1 or 2

Zone 0, 1 or 2 (optional)

------

------

c)

"AEx" symbol

"Ex" symbol

"Ex" symbol

"EEx" symbol

d)

Protection Method symbol(s)

Protection Method symbol(s)

Protection Method symbol(s)

Protection Method symbol(s)

e)

Gas Groups IIA, IIB or IIC

Gas Groups IIA, IIB or IIC

Gas Groups IIA, IIB or IIC

Gas Groups IIA, IIB or IIC

f)

Temperature Codes T1 - T6

Temperature Codes T1 - T6

Temperature Codes T1 - T6

Temperature Codes T1 - T6

a) Indicates explosive gas atmospheres.

b) Indicates likelihood that explosive gas atmosphere is present when the equipment is operating.

c) Symbol for apparatus for use in explosive atmospheres. Internationally (including Canada), the symbol "Ex" is used. In the U.S. only, the 1999 NEC requires the symbol "AEx" instead of "Ex". In Europe only, the symbol "EEx" is used.

d) Indicates the method of protection used to prevent ignition of the explosive gas atmospheres.

e) Indicates the ignition - related properties of the explosive gas atmospheres.

f) Indicates the maximum surface temperature of the equipment under normal operating conditions.

Markings Required for Division-Based Zone Certifications

 

U.S.

Canada

a)

Class I

Class I

b)

Zone 0, 1 or 2

Zone 0, 1 and 2

c)

Gas Groups IIA, IIB, or IIC

Gas Groups IIA, IIB, or IIC

d)

Temperature Codes T1-T6

 Temperature Codes T1-T6


a) Indicates explosive gas atmospheres.

b) Indicates likelihood that explosive gas atmosphere is present when the equipment is operating.

c) Indicates the ignition - related properties of the explosive gas atmospheres.

d) Indicates the maximum surface temperature of the equipment under normal operating conditions.

 

 
 