NYY - PVC LOW VOLTAGE CABLE 600 -1000 VOLT

NYY - Single Core :

Type : NYY - 0,6/1 kV (SPLN. 43 -1 : 1994)

(PVC Insulated and Sheathed) Size : 1 x 1,5 - 500 mm2

MECHANICAL PROPERTIES

 
Size 

mm2

Conductor
Insulation Thickness mm

 

Jacket Thickness mm 
Approx. Overall Dia. mm

 

Approx. Net Weight kg/ km
Standard Reel Length m
Delivery Form
Construction
No. of wire
1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

500

 

re/rm

re/rm

re/rm

re/rm

re/rm

re/rm

rm

rm

rm

rm

rm

rm

rm

rm

rm

rm

rm

rm

 

1(7)

1(7)

1(7)

1(7)

1(7)

1(7)

7

7

19

19

19

37

37

37

61

61

61

61

 

0.8

0.9

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

3.0

 

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

2.0

2.0

2.0

2.2

2.2

 

6.8

7.4

8.0

8.5

9.4

10.8

12.5

13.8

15.8

17.2

19.4

21.0

23.0

26.1

29.2

31.3

35.1

38.9

 

64

80

103

128

173

253

366

470

634

832

1114

1360

1679

2131

2764

3294

4210

5239

 

100

100

100

100

100

500

500

500

500

500

500

500

500

500

500

500

500

250

 

COIL

COIL

COIL

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

 

ELECTRICAL PROPERTIES

 
Size 

mm2

Resistance at 20o C
Current Carrying Capacity
Approx. Reactance per- Conductor Ohm/km
Short Circuit Current at 1 Sec. kA
Test Voltage

kV / 10 min

Conductor DC Calculated Ohm/km
Insulation 

M.Ohm.km

Ground 30o C A
Air 30o C A
1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

500

 

11.9

7.14

4.47

2.97

1.77

1.12

0.708

0.514

0.379

0.262

0.189

0.150

0.122

0.0972

0.0740

0.0590

0.0461

0.0366

 

62

57

52

44

36

26

26

22

22

19

18

16

16

16

16

15

14

14

 

33

45

58

74

98

98/107

125/138

151/165

178/196

218/240

263/289

298/329

338/374

383/418

436/481

490/552

579/632

659/730

 

26

35

46

58

80

86/100

120/135

145/170

180/205

225/260

280/320

330/375

380/430

440/490

530/590

610/680

740/920

860/960

 

-

-

-

-

-

0.110/0.254

0.107/0.2420

0.097/0.228

0.096/0.189

0.094/0.210

0.091/0.203

0.088/0.196

0.086/0.192

0.086/0.184

0.082/0.174

0.082/0.170

0.078/0.163

0.078/0.157

 

0.17

0.29

0.64

0.70

1.16

1.86

2.91

4.07

5.81

8.14

11.05

13.95

17.44

21.51

27.91

34.88

46.51

58.14

 

4

4

4

4

4

4

4

4

4

4

4

4

4

4

4

4

4

4

 

NYY - 2 Cores :

Type : NYY - 0,6/1 kV (SPLN. 43 -1 : 1994)

(PVC Insulated and Sheathed) Size : 2 x 1,5 - 500 mm2

MECHANICAL PROPERTIES

 
Size 

mm2

Conductor
Insulation Thickness mm

 

Jacket Thickness mm 
Approx. Overall Dia. mm

 

Approx. Net Weight kg/ km
Standard Reel Length m
Delivery Form
Construction
No. of wire
1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

 

re/rm

re/rm

re/rm

re/rm

re/rm

re/rm

rm

rm

sm

sm

sm

sm

sm

 

1(7)

1(7)

1(7)

1(7)

1(7)

1(7)

7

7(19)

19

19

19

37

37

 

0.8

0.9

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

 

1.8

1.8

1.8

1.8

1.8

1.8

2.0

2.0

2.0

2.0

2.2

2.2

2.6

 

11.8

12.9

13.9

14.9

16.9

19.9

23.8

26.9

30.5

32.8

37.8

41.5

45.8

 

172

218

282

342

459

668

1035

1312

1749

2234

2984

3567

4539

 

500

500

500

500

500

500

500

500

500

500

500

500

300

 

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM 

DRUM

 

ELECTRICAL PROPERTIES

 
Size 

mm2

Resistance at 20o C
Current Carrying Capacity
Approx. Reactance per- Conductor Ohm/km
Short Circuit Current at 1 Sec. kA
Test Voltage

kV / 10 min

Conductor DC Calculated Ohm/km
Insulation 

M.Ohm.km

Ground 30o C A
Air 30o C A
1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

 

12.10

7.28

4.56

3.03

1.81

1.14

0.74

0.524

0.387

0.268

0.193

0.153

0.124

 

62

57

52

44

36

26

26

22

22

19

18

16

16

 

27

36

47

59

78

102

134

160

187

230

280

320

355

 

21

29

38

48

66

90

120

150

180

230

275

320

375

 

0.108

0.104

0.100

0.094

0.088

0.083

0.080

0.077

0.077

0.074

0.074

0.072

0.072

 

0.17

0.29

0.46

0.70

1.16

1.86

2.91

4.07

5.81

8.14

11.05

13.95

17.44

 

4

4

4

4

4

4

4

4

4

4

4

4

4

 

NYY - 3 Cores :

Type : NYY - 0,6/1 kV (SPLN. 43 -1 : 1994)

(PVC Insulated and Sheathed) Size : 3 x 1,5 - 500 mm2
 
 

MECHANICAL PROPERTIES

 
Size 

mm2

Conductor
Insulation Thickness mm

 

Jacket Thickness mm 
Approx. Overall Dia. mm

 

Approx. Net Weight kg/ km
Standard Reel Length m
Delivery Form
Construction
No. of wire
1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

 

re/rm

re/rm

re/rm

re/rm

re/rm

re/rm

rm

rm

sm

sm

sm

sm

sm

sm

sm

sm

 

1(7)

1(7)

1(7)

1(7)

1(7)

1(7)

7

7(19)

19

19

19

37

37

37

61

61

 

0.8

0.9

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

 

1.8

1.8

1.8

1.8

1.8

1.8

2.0

2.0

2.0

2.0

2.2

2.2

2.6

2.6

2.6

3.0

 

11.9

13.5

14.9

15.8

17.8

21.8

25.8

27.9

27.9

31.7

35.9

38.8

42.8

46.8

57.9

56.7

 

197

256

332

415

565

884

1304

1672

1947

2615

3469

4219

5236

6479

8104

10022

 

500

500

500

500

500

500

500

500

500

500

500

500

300

300

300

300

 

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM 

DRUM

DRUM

DRUM

DRUM

 

ELECTRICAL PROPERTIES

 
Size 

mm2

Resistance at 20o C
Current Carrying Capacity
Approx. Reactance per- Conductor Ohm/km
Short Circuit Current at 1 Sec. kA
Test Voltage

kV / 10 min

Conductor DC Calculated Ohm/km
Insulation 

M.Ohm.km

Ground 30o C A
Air 30o C A
1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

 

12.10

7.28

4.56

3.03

1.81

1.14

0.74

0.524

0.387

0.268

0.193

0.153

0.134

0.0991

0.0754

0.0601

 

62

57

52

58

36

26

26

22

22

19

18

16

16

16

16

14

 

24

32

41

52

69

89

116

138

165

205

245

285

315

355

415

465

 

18

25

34

44

60

80

105

130

160

200

245

285

325

375

435

500

 

0.108

0.104

0.100

0.094

0.088

0.083

0.080

0.077

0.077

0.074

0.074

0.072

0.072

0.072

0.072

0.072

 

0.17

0.29

0.46

0.70

1.16

1.86

2.91

4.07

5.81

8.14

11.05

13.95

17.44

21.51

27.91

34.88

 

4

4

4

4

4

4

4

4

4

4

4

4

4

4

4

4

 


 
 

NYY - 4 Cores :

Type : NYY - 0,6/1 kV (SPLN. 43 -1 : 1994)

(PVC Insulated and Sheathed) Size : 4 x 1,5 - 500 mm2
 
 

MECHANICAL PROPERTIES

 
Size 

mm2

Conductor
Insulation Thickness mm

 

Jacket Thickness mm 
Approx. Overall Dia. mm

 

Approx. Net Weight kg/ km
Standard Reel Length m
Delivery Form
Construction
No. of wire
1.5

2.5

4

6

10

16

25

35

50

70

95

120

185

240

300

 

re/rm

re/rm

re/rm

re/rm

re/rm

re/rm

rm

rm

sm

sm

sm

sm

sm

sm

sm

 

1(7)

1(7)

1(7)

1(7)

1(7)

1(7)

7

7

19

19

19

37

37

61

61

 

0.8

0.9

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.6

1.6

1.6

2.0

2.2

2.4

 

1.8

1.8

1.8

1.8

1.8

1.8

2.0

2.0

2.0

2.2

2.2

2.2

2.6

3.0

3.4

 

12.9

14.5

15.9

16.8

18.9

23.9

27.9

30.9

30.7

33.9

39.5

42.7

51.9

57.9

65.8

 

227

298

398

505

699

1119

1627

2098

3207

3207

4227

5528

8035

10635

13345

 

500

500

500

500

500

500

500

500

500

500

500

300

300

300

300

 

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM 

DRUM

DRUM

DRUM

 

ELECTRICAL PROPERTIES

 
Size 

mm2

Resistance at 20o C
Current Carrying Capacity
Approx. Reactance per- Conductor Ohm/km
Short Circuit Current at 1 Sec. kA
Test Voltage

kV / 10 min

Conductor DC Calculated Ohm/km
Insulation 

M.Ohm.km

Ground 30o C A
Air 30o C A
1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

 

12.10

7.28

4.56

3.03

1.81

1.14

0.74

0.524

0.387

0.268

0.193

0.153

0.124

0.0991

0.0754

0.0601

 

62

57

52

44

36

26

26

22

22

19

18

16

16

16

16

14

 

24

32

41

52

69

89

116

138

165

205

245

280

315

355

415

465

 

18

25

34

44

60

80

105

130

160

200

245

285

325

370

435

500

 

0.115

0.110

0.107

0.100

0.094

0.090

0.086

0.083

0.083

0.082

0.080

0.080

0.080

0.080

0.079

0.079

 

0.17

0.29

0.46

0.70

1.16

1.86

2.91

4.07

5.81

8.14

11.05

13.95

17.44

21.51

27.91

34.88

 

4

4

4

4

4

4

4

4

4

4

4

4

4

4

4

4

 


 
 

NYY - 5 Cores :

Type : NYY - 0,6/1 kV (SPLN. 43 -1 : 1994)

(PVC Insulated and Sheathed) Size : 5 x 1,5 - 500 mm2
 
 

MECHANICAL PROPERTIES

 
Size 

mm2

Conductor
Insulation Thickness mm

 

Jacket Thickness mm 
Approx. Overall Dia. mm

 

Approx. Net Weight kg/ km
Standard Reel Length m
Delivery Form
Construction
No. of wire
1.5

2.5

4

6

10

16

25

35

50

 

re/rm

re/rm

re/rm

re/rm

re/rm

re/rm

rm

rm

rm

 

1(7)

1(7)

1(7)

1(7)

1(7)

1(7)

7

7

19

 

0.8

0.9

1.0

1.0

1.0

1.0

1.2

1.2

1.4

 

1.8

1.8

1.8

1.8

1.8

2.0

2.0

2.0

2.0.

 

13.8

15.5

16.8

18.6

20.8

25.8

29.9

33.6

38.6

 

252

349

469

593

829

1333

1919

2493

3429

 

500

500

500

500

500

500

500

500

500

 

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

DRUM

 

ELECTRICAL PROPERTIES

 
Size 

mm2

Resistance at 20o C
Current Carrying Capacity
Approx. Reactance per- Conductor Ohm/km
Short Circuit Current at 1 Sec. kA
Test Voltage

kV / 10 min

Conductor DC Calculated Ohm/km
Insulation 

M.Ohm.km

Ground 30o C A
Air 30o C A
1.5

2.5

4

6

10

16

25

35

50

 

12.10

7.28

4.56

3.03

1.81

1.14

0.74

0.524

0.387

 

62

57

52

44

36

26

26

22

22

 

24

32

41

52

69

89

116

138

165

 

18

25

34

44

60

80

105

130

160

 

0.115

0.110

0.107

0.100

0.094

0.090

0.086

0.083

0.083

 

0.17

0.29

0.46

0.70

1.16

1.86

2.91

4.07

5.81

 

4

4

4

4

4

4

4

4

4