Watchdog ..
3.3 Diagnostic messages for basic initialization and after

fatal System errors


Diagnostic Message Display: -0

Cause:
The data storage for the controller is tested for its functional capability.  If an error is detected, this display will remain.

Remedy:
The drive controller is defective (DRP3) and must be exchanged.


Diagnostic Message Display: -1

Cause:
The data storage for the DSS 2.1 Module is tested for its functional capability. If an error is detected, this display will remain.

Remedy:
The DSS Module or the connection to the main device is defective.

· If DSS module is defective > exchange

· If drive controller is defective > exchange


Diagnostic Message Display: -2

Cause:
Makeup of the parameter structure. If the EPROMS are exchanged for another version of the firmware, the parameter memory on the programming module is erased (duration appx. 5 sec.).


Diagnostic Message Display: -3

Cause:
The motor type and the type of the motor feedback are determined by reading their parameter storage areas.


Diagnostic Message Display: -5

During basic initialization, an error was reported by the coprocessor.

Cause:
1. Control voltage error (+24 V or +/-15 V). 2. +/-10 V - error.

Remedy:
For 1. Check the control voltage supply.

For 2. Replace the drive.


Diagnostic Message Display: -6

Cause:
A fatal processor or program error was encountered.

Remedy:
The error in question is a system error. Please contact the appropriate software development company.


Diagnostic Message Display: Watchdog ..

Cause:
A fatal processor or program error (Watchdog) was encountered.

Remedy:
Replace the drive.