3.3 Diagnostic messages for basic initialization and after fatal System errors
Diagnostic Message Display: -0
Cause:
The data storage for the controller is tested for its functional capability. If an
error is detected, this display will remain.
Remedy:
The drive controller is defective (DRP3) and must be exchanged.
Diagnostic Message Display: -1
Cause:
The data storage for the DSS 2.1 Module is tested for its functional capability. If an
error is detected, this display will remain.
Remedy:
The DSS Module or the connection to the main device is defective.
· If DSS module is defective > exchange
· If drive controller is defective > exchange
Diagnostic Message Display: -2
Cause:
Makeup of the parameter structure. If the EPROMS are exchanged for another version of the
firmware, the parameter memory on the programming module is erased (duration appx. 5
sec.).
Diagnostic Message Display: -3
Cause:
The motor type and the type of the motor feedback are determined by reading their
parameter storage areas.
Diagnostic Message Display: -5
During basic initialization, an error was reported by the
coprocessor.
Cause:
1. Control voltage error (+24 V or +/-15 V). 2. +/-10 V - error.
Remedy:
For 1. Check the control voltage supply.
For 2. Replace the drive.
Diagnostic Message Display: -6
Cause:
A fatal processor or program error was encountered.
Remedy:
The error in question is a system error. Please contact the appropriate software
development company.
Diagnostic Message Display: Watchdog ..
Cause:
A fatal processor or program error (Watchdog) was encountered.
Remedy:
Replace the drive.
|