4.3 Diagnostic messages for basic initialization
and after fatal System errors
Diagnostic Message Display: -0
The writable data storage of the drive controller is tested for
its functional capability. If an error is detected, this display will remain.
Diagnostic Message Display: -1
The hardware of the amplifier is beig initialized.
Diagnostic Message Display: -2
Cause:
The control supply voltage of the encoder is missing.
Remedy:
Exchange the hardware.
Diagnostic Message Display: -3
Initializing the parameters from the NovRam and calculating the
respective data depending from the parameter contents.
Diagnostic Message Display: -4
Initializing and checking the command communication.
Diagnostic Message Display: -5
Initializing the system control.
Diagnostic Message Display: -6
Starting the system control.
Diagnostic Message Display: E1
Cause:
Processor fault, caused by static discharge, program error or
hardware fault. More information is available via a terminal connected to the RS-232
interface.
Remedy:
Switch the amplifier off and on again; if the fault is still
present, exchange the hardware. In any case inform the customer service.
Diagnostic Message Display: E2
Cause:
Test of the RAM on the programming module has shown an error. RAM
defective or not plugged properly.
Remedy:
Switch off, check the plug connection and switch on again; if the
error happens agains, exchange the firmware module.
Diagnostic Message Display: E3
Cause:
Caused by a hardware fault or by a static discharge, the 1 st
watchdog of the amplifier has triggered.
Remedy:
Switch the amplifier off and on again; if E3 appears again, exchange
the amplifier. In any case inform the customer service. Please explain the exact
circumstances under which the error occurred.
Diagnostic Message Display: E4
Cause:
Caused by a hardware fault or by a static discharge, the 2 nd
watchdog of the amplifier has triggered.
Remedy:
Switch the amplifier off and on again; if E4 appears again, exchange
the amplifier. In any case inform the customer service.
Diagnostic Message Display: E5
Cause:
Test of the dual-port-RAM for command communication failed. Maybe
the hardware for command communication is not plugged on properly.
Remedy:
Check the plug connection; if OK, exchange the amplifier. |