3. Fault messages

The red "FAULT" lamp lights up in case of a fault. The fault is annunciated on the display and the display flashes.

The safety guidelines must be noted prior to working on any wiring or when replacing a unit (see doc.no. 209-0041-4109).


BLEEDER

Bleeder overload

- Bleeder monitor has been actuated because of overheating.

- The bleeder in the drive controller is defective or no bleeder is installed.
Remedy
1. Check to see whether a bleeder resistor has been installed in the drive controller (wire filament). If yes, then let the drive controller cool down for at least 15 minutes. Then switch back on. If fault is still displayed, replace drive controller! Note the safety guidelines when replacing a unit! Note the guidelines on handling the programming module! ->See doc. no. 209-0041-4109-02!

- If the drive controller is not equipped with a bleeder resistor (type designation ...-W1), then <256> has been incorrectly set in the value of parameter FUNCT2 (A06).
Remedy
2. Reduce parameter value by 256! ->See doc. no. 209-0041-4109-02!


BS
(only with KDA)

Bridge fuse

The current limit, set at the electronic fuse in the drive controller, was exceeded.
Remedy
1. Check motor supply line for short circuit and ground fault. Check the motor for windings and ground fault.


DACFAULT

Error in digital/analogue converter

Error on the CDR card
Remedy
1. Replace drive controller!


ADRERR

Program error
Remedy
Update software


BUS-ERR

Program error
Remedy
Update software


CDR16MHZ

Incorrect software/drive controller combination
Remedy
Replace software


CDR S001

Incorrect software/drive controller combination
Remedy
Replace software


DC-FAULT
(only with RAC)

The DC bus is not loading up properly after the power contactor has been switched on.
Remedy

1. Switch drive controller and power feed off!

2. Check mains connection terminals (X14/L1,L2,L3) whether cable is firmly in place!

3. In the RAC2, check the DC bus voltage (X6/L+,L-) for short-circuit and eliminate!

4. Switch drive controller back on! If fault message continues, replace drive controller!

Note the safety guidelnes on replacing the unit!
Note the guidelines on handling the programming module! ->See doc. no. 209-0041-4109-02


EARTH CON

Ground fault in motor cable or DC bus.

Remedy
1. Switch drive controller off

2. Check motor power cable (control cabinet leadthrough?)

3. Check motor for ground fault

4. Check the DC bus wiring in the KDA/TDA for ground fault

5. Replace faulty components (motor, drive controller, cable) or correct faulty wiring!


EEPROM

Programming error in parameter memory

There is no EEPROM (IC3) on the programming module or the plugged-in EEPROM is defective.

Remedy
1. Switch drive controller off. Insert appropriate EEPROM into programming module or replace existing EEPROM.

2. If this is not possible, replace programming module! Note the handling of the programming module! Enter the machine-specific parameters specified in the documentation! ->See doc. no. 209-0041-4109-02!


EPRFAULT

Loss of data in program memory

The contents of the program memory (EPROM) have changed.

Remedy
1. The message can be reset by hitting the red key. The drive may continue to run. We do not guarantee problem-free operation.

2. Replace the programming module.


FEEDBACK

Motor encoder error

Wrong value in parameter FEEDBACK (M03). The feedback on the motor requires a different parameter value.

Remedy
1. Set parameter value in M03 that corresponds to the motor feedback type. ->See doc. no. 209-0041-4109-02! Defective or wrong feedback cable

Remedy
2. Repair or replace feedback cable.


GEARBOX

Gear switching error

The gear cannot be switched, or the acknowledgement of the gear step is either not given or it comes too late (see control inputs SPEED1 and SPEED2 (X2/35,36), see Figure 1.4).

Remedy
1. Switch drive controller off.

2. Check the wiring of the contactor, acknowledgement contacts and the torque motor to see whether they correspond to the terminal diagram of INDRAMAT.

3. Check the indexing mechanism. ->See doc. no. 209-0041-4109-02


HOMING

Reference impulse search
Is normally cancelled after one spindle rotation. Spindle referencing signal has not arrived at control input EXT POS (X2/37) (also see Figure 1.4)

Remedy
1. Replace drive controller.

2. Check spindle referencing switch for proper connection and cam angle! ->See doc. no. 209-0041-4109-02 Zero impulse of the spindle or the motor feedback does not arrive.

Remedy
1. Check feedback cables, replace if damaged!


I< >ITYP

Parameter M17 incorrectly programmed
The data in parameter M17 does not agree with the rated current of the drive controller.

Remedy
Reprogram parameter M17.


I > ITYP

Parameter M06 incorrectly programmed
The value in parameter M06 is greater than the rated current of the drive.

Remedy
Reprogram parameter M06.


KKTEMP

Heatsink overtemperature
The heatsink of the drive controller is too hot. The message TEMPWARN (X2/9) was ignored by the control unit. The drive controller has switched itself off!

Remedy
1. Check the blowers of the drive, the air channels, the load cycle, the ambient temperature as well as the connection of the signal output TEMPWARN (X2/9) to the control unit!

2. Clear fault message once the problem has been eliminated by hitting the red key in the center of the keypad!


MOTTEMP

 

Motor overtemperature
The temperature of the motor winding has reached 155°C. Message TEMPWARN (X2,9) was ignored. The drive controller has switched itself off.

Remedy
1. Check the blowers of the drive, the air channels, the load cycle, the ambient temperature as well as the connection of the signal output TEMPWARN to the control unit!

2. Clear fault message once the problem has been eliminated by hitting the red key in the center of the keypad!


MOTOR1/2

Motor switching error
The acknowledgement for motor contactor switchover is missing or it arrives too late (see control inputs SPEED1 and SPEED2 (X2/35,36), see Figure 1.4).

Remedy
1. Replace drive controller.

2. Check contactor wiring and acknowledgement contacts for compliance with the terminal diagram of INDRAMAT. ->See doc. no. 209-0041-4109-02!


NOMAINS

(only with RAC 3)

No mains voltage
No voltage at the mains terminals X14/L1,L2,L3 , or the voltage applied is too low.

Remedy
1. Check mains!


NO TEMP

Error in motor temperature detector
The connection between the thermistor of the motor and the drive controller is disrupted or the thermistor is defective (this message comes approximately ten minutes after the fault occurs).

Remedy
1. Check the thermistor connection. There are always two thermistors in 2AD and 1MB motors. Only one can be connected to the drive controller!

2. Check thermistor: R20°C= approx. 40KOhm, R80°C= approx. 3.5kOhm, R140°C= approx. 565 Ohm ±5 % each. If the measured values exceed this range, replace thermistor, motor (2AD) or stator (1MB)!


NO 8V

8 V - Control voltage faulty
The internal 8V supply of the drive controller is disrupted.

Remedy
1. Replace drive controller!


NO 15V

15 V - Control voltage faulty
The internal ± 15V supply of the drive controller is disrupted.

Remedy
1. With the KDA/TDA, check whether bus connection cable for control voltage is firmly in place. If fault is signalled, replace drive controller!

2. With an RAC, replace drive controller or call INDRAMAT customer service!


NO 24V

24 V - Control voltage faulty
The internal ± 24V supply of the drive controller is disrupted.

Remedy
1. With the KDA/TDA, check whether bus connection cable for control voltage is firmly in place. If fault is signalled, replace drive controller!

2. With an RAC, replace drive controller or call INDRAMAT customer service!


NO 8 MHZ

Incorrect software-drive controller combination

Remedy
Replace software


NO 24 VEX

There is no external application of voltage for the control and signal outputs (X2/1 und 19), or these are incorrectly polarized or exceed tolerance range.

Remedy
1. Check connection and voltage level of external +24V . The voltage level must range between 18V and 36V. If the external +24V is in order, then the fault message should clear of its own accord.

2. If there is no external +24V/0V, then the internal +24V/OV of the drive controller can be used (apply bridge from +24Vint/OVint to +24Vext/ OVext (connector X2)).


NO KDA

NO RAC2

NO RAC3

NO RAC4

NO TDA

Parameter M17 incorrectly programmed

Remedy
Reprogram parameter M17.


OPCODE F

Program error

Remedy
Update software


OVER VOLT

(only with RAC)

Overvoltage

The mains voltage exceeds the nominal voltage connection by more than 15%. It is not possible to switch on the mains contactor in the unit.

Remedy

1. Check mains, transformer may have to be connected to adapt mains voltage.


PARALOST

Data loss in parameter storage
There are no parameter values in the programming module. These were either cleared or not stored.

Remedy
1. Move the operating mode switch to the left and press the red key. This loads general base parameters which can set the drive in motion. If ‹BASISPAR" appears on the display, then loading is completed. Pressing the red key again will bring the drive into parameter mode. The base parameters are not optimal for the drive and should be replaced by optimized values (AS../...) (supplied as part of the parameter protocol of the programming module). ->See doc. no.209-0041-4109-02.


PHASE

(only with RAC 3)

There is no right-rotational field or one of the three phases is missing (with RAC 3 only phase failure)

Remedy
1. Check mains


POS ERROR

Positioning error
Lag error monitor has been actuated during spindle positioning with spindle reference switch. Drive cannot comply with position command value.

Remedy
1. Check spindle for jamming, sluggishness and defects in the coupling component.

2. Check whether torque reduction of the drive is active (+24V at control input MD-RED (X2/28), see Figure 4)!

3. Reduce positioning speed POSRPM with a lesser value in parameter P18, Q18, R18 or S18! ->See doc. no. 209-0041-4109-02!


RAM FAULT

(only with RAC)

Error in data memory
Error while checking RAM memory in drive controller.

Remedy
1. Replace drive controller.


RSK FAULT

(only with RAC 3)

The RSK printed circuit board not working.

Remedy
1. Switch drive controller off. If message still comes after switching unit back on, then replace the drive controller.


RSCURNT

(only with RAC 3)

Overcurrent during feedback

Remedy
1. Check mains


S-CIRCUIT

Short circuit in motor cable

Remedy
1. Replace drive controller.

2. Check motor power cable (control cabinet leadthrough?). Replace ifdamaged.

3. Check motor windings resistance. In the event of a short-circuit, replace motor (2AD) or stator (1MB)!


SPINDLE

Spindle encoder monitor
No information is being received from spindle position encoder.

Remedy
1. Check the coupling component of spindle to the drive!

2. Check the coupling component of the spindle position encoder to the spindle!

3. Check electrical connections of spindle feedback and drive controller!


X12 IGS

Incorrect drive controller configuration
Two-motor changeover was programmed in connection with incremental encoder interface.

Remedy
1. Remove two-motor changeover by reprogramming parameter.

2. Remove inremental encoder interface (IGS card) from the drive controller.