CHARGING CYLINDER CORRECTION FACTORS

 

Most refrigerant blends are suitable for use with charging cylinders. The following temperature correction factors are used with the standard CFC-12, HCFC-22 scale:

Simply multiply the quantity of refrigerant required, by weight, by the correction factor and read on the HCFC-22 scale. Remember that blends need to come out of the container as a liquid to prevent fractionation. (The best method is to use Thermal Engineering's model 7701 Rapid Vapor Charging Device.)

REFRIGERANT

CORRECTION FACTOR

ASHRAE#

Brand Name

R410A

AZ20

1.15

R507

AZ50

1.10

R404A

HP62

1.14

R402A

HP80

1.05

R402B

HP81

1.04

R401A

MP39

1.00*

R401B

MP66

1.00*

R401C

MP52

.99

R134a (not a blend)

.99**

Charging cylinders are perfect for carrying small amounts of refrigerant that can be purchased in larger, more economical containers. There are also a great alternative when an electronic scale is not available.

*These can be read directly off the R22 scale.

** Purchase a printed HFC-134a scale if using this refrigerant exclusively.

Courtesy of Thermal Engineering Co.