WEEK 09: DESIGN NOTES: TRANSFORMER: CORE-TYPE


Legend: : Formula | : Limits, Range | : Assumption, etc.


Sections: Guaranteed Losses | Windings | Magnetic Circuit | Efficiency | Regulation | Tank & Temp. Rise

Guaranteed Losses

Item A. Total Loss at Full Load, W
W = KVA(1 - %e) / %e
Where: KVA = KVA rating
%e = per cent efficiency at full load
For the per cent efficiency at full load, %e, see performance table.

Item B. Total Loss at ¼ Load, W¼
W¼ = KVA(1 - %e¼) / %e¼
Where: KVA = KVA rating
%e¼ = per cent efficiency at ¼ full load
For the per cent efficiency at full load, %e¼, see performance table.

Item C. Full Load Copper Loss, WCu
WCu = WFL - W¼ / (1 - ¼²)
Where: W¼ = total loss when the load is ¼KVA
¼ = ¼ times the full load rating
For the per cent efficiency at full load, %e¼, see performance table.

Item D. Full Load Core Loss, WFe
WFe = WFL - WCu

Item 1. Volts per turn from formula, Vtformula
Vtformula = 1/c x ÖKVA

Volts per turn actual, Vtactual
Will be solved after determining the finalization of the Total Number of turns, using: Vtactual = VH.T./TH.T.

 Items 02 - 23